OpenStudio Results

Model Summary


Information Value Units
Building Name NECB 2011-HighriseApartment-NECB HDD Method-CAN_MB_Brandon.711400_CWEC.epw created: 2017-06-30 12:56:51 +0000 building_name
Net Site Energy 4,017,001 kBtu
Total Building Area 84,351 ft^2
EUI (Based on Net Site Energy and Total Building Area) 47.62 kBtu/ft^2
OpenStudio Standards Building Type HighriseApartment

Value
Weather File Brandon MB CAN WYEC2-e-14997 WMO#=711400
Latitude 49.92
Longitude -100.0
Elevation 1342 (ft)
Time Zone -6.0
North Axis Angle 0.00
ASHRAE Climate Zone

Maximum Dry Bulb (F) Daily Temperature Range (R) Humidity Value Humidity Type Wind Speed (mph) Wind Direction
BRANDON ANN CLG .4% CONDNS DB=>MWB 87.08 22.5 68.18 Wetbulb [F] 11.41 180.0
BRANDON ANN CLG .4% CONDNS WB=>MDB 82.22 22.5 71.6 Wetbulb [F] 11.41 180.0
BRANDON ANN HTG 99.6% CONDNS DB -28.3 0.0 -28.3 Wetbulb [F] 9.17 280.0

Time Setpoint Not Met Time (hr)
During Heating 0.0
During Cooling 33.5
During Occupied Heating 0.0
During Occupied Cooling 33.5

Tolerance for Time Setpoint Not Met Temperature (F)
Heating 1.8
Cooling 1.8

Annual Overview

One or more tables in Annual Overview section returned false and was skipped.

End Use Consumption (kBtu)
Heating 2,107,538
Cooling 243,674
Interior Lighting 299,122
Exterior Lighting 0
Interior Equipment 468,544
Exterior Equipment 0
Fans 218,007
Pumps 1,668
Heat Rejection 123
Humidification 0
Heat Recovery 95
Water Systems 678,229
Refrigeration 0
Generators 0

Fuel Consumption (kBtu)
Electricity 4,017,001
Natural Gas 0
Additional Fuel 0
District Cooling 0
District Heating 0

End Use Consumption (kWh)
Heating 617,658
Cooling 71,414
Interior Lighting 87,664
Exterior Lighting 0
Interior Equipment 137,317
Exterior Equipment 0
Fans 63,892
Pumps 489
Heat Rejection 36
Humidification 0
Heat Recovery 28
Water Systems 198,769
Refrigeration 0
Generators 0

Monthly Overview


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total
Heating 126898.89 98265.0 73288.61 34803.33 17985.19 8156.69 4621.31 6343.64 17348.5 34294.17 74340.56 121313.33 617659.22
Cooling 166.67 236.93 819.89 3468.42 6917.78 13958.61 18678.64 16320.19 6656.06 3682.25 405.75 101.49 71412.67
Interior Lighting 7444.64 6725.47 7454.72 7191.47 7454.72 7211.64 7434.56 7454.72 7201.56 7444.64 7211.64 7434.56 87664.33
Exterior Lighting
Interior Equipment 11662.0 10534.06 11666.97 11279.42 11666.97 11289.33 11657.06 11666.97 11284.39 11662.0 11289.33 11657.06 137315.56
Exterior Equipment
Fans 3305.5 3021.08 3574.08 4519.64 5923.56 8193.42 9511.61 8803.53 5724.39 4744.33 3297.42 3274.36 63892.92
Pumps 18.75 23.28 40.4 44.02 52.93 53.04 51.76 54.87 46.3 47.08 35.59 20.04 488.07
Heat Rejection 0.01 0.0 0.25 1.47 3.22 6.42 9.56 9.43 3.43 2.72 0.16 0.01 36.67
Humidification
Heat Recovery 0.1 0.18 4.85 12.53 9.53 0.29 27.46
Water Systems 18094.83 16735.22 18550.92 17460.17 17352.75 15903.42 15590.53 15241.69 14814.22 15629.03 16021.44 17376.36 198770.58
Refrigeration
Generators
Total 167591.3 135541.05 115395.84 78768.03 67357.3 64777.42 67567.55 65904.58 63079.12 77506.21 112601.88 161177.21 1177267.48

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Heating 380.1466 352.3497 254.9265 82.8642 27.1881 17.5302 175.3898 296.1488 331.8993
Cooling 0.2931 15.9436 56.6594 60.4934 43.8909 17.8091 0.035
Interior Lighting 21.5307 21.5307 21.5307 37.2956 37.2956 37.2956 37.2956 37.2956 37.2956 21.5307 21.5307 21.5307
Exterior Lighting
Interior Equipment 28.4158 28.4158 28.4158 31.5045 31.5045 31.5045 31.5045 31.5045 31.5045 28.4158 28.4158 28.4158
Exterior Equipment
Fans 4.5665 4.5665 4.5665 4.3614 10.9364 22.6145 22.9418 17.807 11.7274 4.5665 4.5665 4.5665
Pumps 0.0172 0.0172 0.0172 0.0172 0.0172 0.0172 0.0172 0.0172 0.0172 0.1445 0.0172 0.0172
Heat Rejection
Humidification
Heat Recovery 0.05 0.05 0.05
Water Systems 61.9424 49.4433 43.5464 58.8152 57.865 56.555 48.0201 55.6888 55.5736 47.166 47.4982 60.3034
Refrigeration
Generators
Total 496.62 456.32 353.0 215.15 180.75 204.7 200.32 186.25 171.46 277.25 398.18 446.73

Utility Bills/Rates

No Data to Show for Utility Bills/Rates

Envelope


Construction Net Area (ft^2) Surface Count R Value (ft^2*h*R/Btu)
Customized opaque construction {39bd9822-b0f4-49bb-93f8-9de9fae10b80} to conductance of 0.21 30,317 140 27.04
Customized opaque construction {c25a1619-bd90-4cb3-9e06-0934c38132d0} to conductance of 0.162 8,435 9 35.05

Construction Area (ft^2) Surface Count U-Factor (Btu/ft^2*h*R)
Customized Fenestration: cond=0.220 tvis=0.220 tsol=0.232 11,178 140 0.3874

Description Total (%) North (%) East (%) South (%) West (%)
Gross Window-Wall Ratio 26.94 27.08 26.74 27.08 26.35
Gross Window-Wall Ratio (Conditioned) 26.94 27.08 26.74 27.08 26.35
Skylight-Roof Ratio 0.0

Space Type Breakdown


Space Type Name Floor Area (ft^2) Standards Building Type Standards Space Type
Space Function Corr. < 2.4m wide-sch-G 8,359 Space Function Corr. < 2.4m wide-sch-G
Space Function Dwelling Unit(s) 75,042 Space Function Dwelling Unit(s)
Space Function Office - enclosed 950 Space Function Office - enclosed

Space Type Summary


Definition Value Unit Inst. Multiplier
Space Function Corr. < 2.4m wide-sch-G People Definition 0.0009 people/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Lights Definition 0.7804 W/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Ventilation (outdoor air method Sum) 0.0600 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Dwelling Unit(s) People Definition 0.0016 people/ft^2 1.0
Space Function Dwelling Unit(s) Elec Equip Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Lights Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Ventilation (outdoor air method Sum) 0.0680 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Office - enclosed People Definition 0.0046 people/ft^2 1.0
Space Function Office - enclosed Elec Equip Definition 0.6968 W/ft^2 1.0
Space Function Office - enclosed Lights Definition 1.1055 W/ft^2 1.0
Space Function Office - enclosed Ventilation (outdoor air method Sum) 0.0850 cfm/floor area ft^2

Interior Lighting Summary


Zone Lighting Power Density (W/ft^2) Total Power (W) Schedule Name Scheduled Hours/Week (hr) Actual Load Hours/Week (hr) Return Air Fraction Annual Consumption (kWh)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 1.11 1050.15 NECB-A-LIGHTING 56.27 56.27 0.0000 3080.56

Plug Loads Summary


Electricity Annual Value (kWh)
InteriorEquipment:Electricity:Zone:SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2450.0

Exterior Lighting

No Data to Show for Exterior Lighting

Water Use Equipment


Instance Plant Loop Definition Space Peak Flow Rate (gal/min) Flow Rate Schedule Target Temp Range (F)
F2 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n1 apartment Service Water Use Def 0.06gal/min F2 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n2 apartment Service Water Use Def 0.06gal/min F2 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F2 ne apartment Service Water Use Def 0.06gal/min F2 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 nw apartment Service Water Use Def 0.06gal/min F2 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s1 apartment Service Water Use Def 0.06gal/min F2 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s2 apartment Service Water Use Def 0.06gal/min F2 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 se apartment Service Water Use 0.06gal/min Main Service Water Loop F2 se apartment Service Water Use Def 0.06gal/min F2 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 sw apartment Service Water Use Def 0.06gal/min F2 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n1 apartment Service Water Use Def 0.06gal/min F3 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n2 apartment Service Water Use Def 0.06gal/min F3 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F3 ne apartment Service Water Use Def 0.06gal/min F3 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 nw apartment Service Water Use Def 0.06gal/min F3 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s1 apartment Service Water Use Def 0.06gal/min F3 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s2 apartment Service Water Use Def 0.06gal/min F3 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 se apartment Service Water Use 0.06gal/min Main Service Water Loop F3 se apartment Service Water Use Def 0.06gal/min F3 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 sw apartment Service Water Use Def 0.06gal/min F3 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n1 apartment Service Water Use Def 0.06gal/min F4 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n2 apartment Service Water Use Def 0.06gal/min F4 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F4 ne apartment Service Water Use Def 0.06gal/min F4 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 nw apartment Service Water Use Def 0.06gal/min F4 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s1 apartment Service Water Use Def 0.06gal/min F4 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s2 apartment Service Water Use Def 0.06gal/min F4 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 se apartment Service Water Use 0.06gal/min Main Service Water Loop F4 se apartment Service Water Use Def 0.06gal/min F4 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 sw apartment Service Water Use Def 0.06gal/min F4 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n1 apartment Service Water Use Def 0.06gal/min F6 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n2 apartment Service Water Use Def 0.06gal/min F6 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F6 ne apartment Service Water Use Def 0.06gal/min F6 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 nw apartment Service Water Use Def 0.06gal/min F6 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s1 apartment Service Water Use Def 0.06gal/min F6 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s2 apartment Service Water Use Def 0.06gal/min F6 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 se apartment Service Water Use 0.06gal/min Main Service Water Loop F6 se apartment Service Water Use Def 0.06gal/min F6 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 sw apartment Service Water Use Def 0.06gal/min F6 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n1 apartment Service Water Use Def 0.06gal/min F7 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n2 apartment Service Water Use Def 0.06gal/min F7 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F7 ne apartment Service Water Use Def 0.06gal/min F7 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 nw apartment Service Water Use Def 0.06gal/min F7 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s1 apartment Service Water Use Def 0.06gal/min F7 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s2 apartment Service Water Use Def 0.06gal/min F7 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 se apartment Service Water Use 0.06gal/min Main Service Water Loop F7 se apartment Service Water Use Def 0.06gal/min F7 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 sw apartment Service Water Use Def 0.06gal/min F7 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n1 apartment Service Water Use Def 0.06gal/min F8 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n2 apartment Service Water Use Def 0.06gal/min F8 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F8 ne apartment Service Water Use Def 0.06gal/min F8 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 nw apartment Service Water Use Def 0.06gal/min F8 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s1 apartment Service Water Use Def 0.06gal/min F8 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s2 apartment Service Water Use Def 0.06gal/min F8 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 se apartment Service Water Use 0.06gal/min Main Service Water Loop F8 se apartment Service Water Use Def 0.06gal/min F8 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 sw apartment Service Water Use Def 0.06gal/min F8 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n1 apartment Service Water Use Def 0.06gal/min F9 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n2 apartment Service Water Use Def 0.06gal/min F9 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F9 ne apartment Service Water Use Def 0.06gal/min F9 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 nw apartment Service Water Use Def 0.06gal/min F9 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s1 apartment Service Water Use Def 0.06gal/min F9 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s2 apartment Service Water Use Def 0.06gal/min F9 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 se apartment Service Water Use 0.06gal/min Main Service Water Loop F9 se apartment Service Water Use Def 0.06gal/min F9 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 sw apartment Service Water Use Def 0.06gal/min F9 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n1 apartment Service Water Use 0.06gal/min Main Service Water Loop G n1 apartment Service Water Use Def 0.06gal/min G N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n2 apartment Service Water Use 0.06gal/min Main Service Water Loop G n2 apartment Service Water Use Def 0.06gal/min G N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G ne apartment Service Water Use 0.06gal/min Main Service Water Loop G ne apartment Service Water Use Def 0.06gal/min G NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G nw apartment Service Water Use 0.06gal/min Main Service Water Loop G nw apartment Service Water Use Def 0.06gal/min G NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s1 apartment Service Water Use 0.06gal/min Main Service Water Loop G s1 apartment Service Water Use Def 0.06gal/min G S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s2 apartment Service Water Use 0.06gal/min Main Service Water Loop G s2 apartment Service Water Use Def 0.06gal/min G S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G sw apartment Service Water Use 0.06gal/min Main Service Water Loop G sw apartment Service Water Use Def 0.06gal/min G SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n1 apartment Service Water Use 0.06gal/min Main Service Water Loop M n1 apartment Service Water Use Def 0.06gal/min M N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n2 apartment Service Water Use 0.06gal/min Main Service Water Loop M n2 apartment Service Water Use Def 0.06gal/min M N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M ne apartment Service Water Use 0.06gal/min Main Service Water Loop M ne apartment Service Water Use Def 0.06gal/min M NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M nw apartment Service Water Use 0.06gal/min Main Service Water Loop M nw apartment Service Water Use Def 0.06gal/min M NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s1 apartment Service Water Use 0.06gal/min Main Service Water Loop M s1 apartment Service Water Use Def 0.06gal/min M S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s2 apartment Service Water Use 0.06gal/min Main Service Water Loop M s2 apartment Service Water Use Def 0.06gal/min M S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M se apartment Service Water Use 0.06gal/min Main Service Water Loop M se apartment Service Water Use Def 0.06gal/min M SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M sw apartment Service Water Use 0.06gal/min Main Service Water Loop M sw apartment Service Water Use Def 0.06gal/min M SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
Office Service Water Use 0.03gal/min Main Service Water Loop Office Service Water Use Def 0.03gal/min Office 0.03 NECB-A-Service Water Heating 140.0 to 140.0
T n1 apartment Service Water Use 0.06gal/min Main Service Water Loop T n1 apartment Service Water Use Def 0.06gal/min T N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T n2 apartment Service Water Use 0.06gal/min Main Service Water Loop T n2 apartment Service Water Use Def 0.06gal/min T N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T ne apartment Service Water Use 0.06gal/min Main Service Water Loop T ne apartment Service Water Use Def 0.06gal/min T NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T nw apartment Service Water Use 0.06gal/min Main Service Water Loop T nw apartment Service Water Use Def 0.06gal/min T NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s1 apartment Service Water Use 0.06gal/min Main Service Water Loop T s1 apartment Service Water Use Def 0.06gal/min T S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s2 apartment Service Water Use 0.06gal/min Main Service Water Loop T s2 apartment Service Water Use Def 0.06gal/min T S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T se apartment Service Water Use 0.06gal/min Main Service Water Loop T se apartment Service Water Use Def 0.06gal/min T SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T sw apartment Service Water Use 0.06gal/min Main Service Water Loop T sw apartment Service Water Use Def 0.06gal/min T SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0

HVAC Load Profiles


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Average Outdoor Air Dry Bulb (F) -0.4 5.5 19.4 38.6 52.4 61.0 65.7 64.0 52.4 40.9 22.6 4.6
Cooling Load (MBtu) 0.57 0.81 2.8 11.83 23.6 47.63 63.73 55.69 22.71 12.56 1.38 0.35
Heating Load (MBtu) 433.0 335.29 250.07 118.75 61.37 27.83 15.77 21.65 59.2 117.02 253.66 413.94

Zone Conditions


Zone Unmet Htg (hr) Unmet Htg - Occ (hr) < 56 (F) 56-61 (F) 61-66 (F) 66-68 (F) 68-70 (F) 70-72 (F) 72-74 (F) 74-76 (F) 76-78 (F) 78-83 (F) 83-88 (F) >= 88 (F) Unmet Clg (hr) Unmet Clg - Occ (hr) Mean Temp (F)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 62 478 2118 1244 4858 0 0 0 0 0 0 73.5 (F)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 108 379 497 2878 933 3965 0 0 0 0 0 0 72.8 (F)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 108 382 498 2888 914 3970 0 0 0 0 0 0 72.8 (F)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 446 367 317 2980 789 3861 0 0 0 0 0 0 72.5 (F)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 425 374 300 2984 827 3849 1 0 0 0 0 0 72.5 (F)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 15 105 372 1298 1024 5918 28 0 0 0 0 0 73.8 (F)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 14 108 371 1294 1016 5930 27 0 0 0 0 0 73.8 (F)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 208 305 328 1799 915 5201 4 0 0 0 0 0 73.3 (F)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 189 310 336 1835 997 5090 3 0 0 0 0 0 73.3 (F)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 61 462 2094 1203 4940 0 0 0 0 0 0 73.5 (F)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 124 379 477 2851 897 4032 0 0 0 0 0 0 72.8 (F)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 126 382 475 2861 875 4041 0 0 0 0 0 0 72.8 (F)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 470 356 293 2972 777 3892 0 0 0 0 0 0 72.5 (F)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 447 358 287 2966 817 3884 1 0 0 0 0 0 72.5 (F)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 17 109 361 1264 1009 5974 26 0 0 0 0 0 73.8 (F)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 17 109 360 1264 1001 5984 25 0 0 0 0 0 73.8 (F)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 203 310 332 1811 972 5129 3 0 0 0 0 0 73.3 (F)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 198 305 326 1829 990 5109 3 0 0 0 0 0 73.3 (F)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 67 465 2110 1188 4930 0 0 0 0 0 0 73.5 (F)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 139 386 461 2858 895 4021 0 0 0 0 0 0 72.8 (F)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 140 385 467 2860 875 4033 0 0 0 0 0 0 72.8 (F)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 493 345 288 2988 785 3861 0 0 0 0 0 0 72.5 (F)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 472 349 283 2981 819 3855 1 0 0 0 0 0 72.5 (F)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 19 118 369 1292 990 5946 26 0 0 0 0 0 73.8 (F)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 19 118 370 1295 985 5948 25 0 0 0 0 0 73.8 (F)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 221 309 335 1860 974 5058 3 0 0 0 0 0 73.2 (F)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 216 303 328 1867 989 5054 3 0 0 0 0 0 73.2 (F)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 76 494 2146 1196 4848 0 0 0 0 0 0 73.4 (F)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 155 416 436 2900 912 3941 0 0 0 0 0 0 72.7 (F)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 155 417 442 2905 904 3937 0 0 0 0 0 0 72.7 (F)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 531 331 290 3036 803 3769 0 0 0 0 0 0 72.4 (F)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 518 321 285 3045 826 3763 2 0 0 0 0 0 72.5 (F)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 25 139 384 1381 973 5834 24 0 0 0 0 0 73.8 (F)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 25 139 385 1379 979 5831 22 0 0 0 0 0 73.7 (F)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 250 320 320 1942 1006 4919 3 0 0 0 0 0 73.1 (F)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 246 305 330 1939 1017 4920 3 0 0 0 0 0 73.2 (F)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 83 507 2196 1205 4769 0 0 0 0 0 0 73.4 (F)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 165 424 434 2953 931 3853 0 0 0 0 0 0 72.7 (F)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 165 428 437 2947 920 3863 0 0 0 0 0 0 72.7 (F)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 549 323 293 3081 804 3710 0 0 0 0 0 0 72.4 (F)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 534 318 283 3112 807 3704 2 0 0 0 0 0 72.4 (F)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 28 153 397 1432 986 5743 21 0 0 0 0 0 73.7 (F)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 28 152 401 1435 981 5744 19 0 0 0 0 0 73.7 (F)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 271 310 331 1995 992 4858 3 0 0 0 0 0 73.1 (F)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 267 301 331 2005 1008 4845 3 0 0 0 0 0 73.1 (F)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 105 516 2303 1249 4587 0 0 0 0 0 0 73.3 (F)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 182 439 431 3017 999 3692 0 0 0 0 0 0 72.6 (F)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 185 436 431 3028 972 3708 0 0 0 0 0 0 72.6 (F)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 573 310 312 3165 767 3633 0 0 0 0 0 0 72.4 (F)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 556 302 300 3209 787 3604 2 0 0 0 0 0 72.4 (F)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 36 171 408 1534 1062 5531 18 0 0 0 0 0 73.6 (F)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 36 171 409 1540 1060 5526 18 0 0 0 0 0 73.6 (F)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 307 306 340 2090 985 4729 3 0 0 0 0 0 73.0 (F)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 299 295 345 2098 1006 4714 3 0 0 0 0 0 73.0 (F)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0 0 0 0 1 175 595 2536 1235 4218 0 0 0 0 0 0 73.1 (F)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 257 443 429 3262 945 3424 0 0 0 0 0 0 72.4 (F)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 257 445 430 3257 932 3439 0 0 0 0 0 0 72.4 (F)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 626 293 354 3345 663 3479 0 0 0 0 0 0 72.2 (F)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 609 282 360 3361 740 3407 1 0 0 0 0 0 72.2 (F)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 84 249 413 1772 1217 5015 10 0 0 0 0 0 73.4 (F)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 84 253 413 1772 1218 5010 10 0 0 0 0 0 73.3 (F)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 404 278 367 2358 910 4440 3 0 0 0 0 0 72.8 (F)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 391 280 353 2369 939 4425 3 0 0 0 0 0 72.8 (F)
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 0 0 0 0 1 194 581 2197 1320 4467 0 0 0 0 0 0 73.2 (F)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 151 422 482 2984 1086 3635 0 0 0 0 0 0 72.6 (F)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 151 425 483 2986 1061 3654 0 0 0 0 0 0 72.6 (F)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 506 362 328 3086 851 3627 0 0 0 0 0 0 72.4 (F)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 484 364 318 3101 898 3593 2 0 0 0 0 0 72.4 (F)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 18 176 425 1467 1173 5469 32 0 0 0 4 4 73.6 (F)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 18 186 422 1438 1157 5506 33 0 0 0 6 6 73.6 (F)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 250 328 369 1897 1086 4824 6 0 0 0 0 0 73.1 (F)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 71 479 2121 1191 4898 0 0 0 0 0 0 73.5 (F)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 149 398 452 2872 907 3982 0 0 0 0 0 0 72.8 (F)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 148 401 454 2883 877 3997 0 0 0 0 0 0 72.8 (F)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 513 338 284 3010 795 3820 0 0 0 0 0 0 72.5 (F)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 499 332 280 3014 815 3819 1 0 0 0 0 0 72.5 (F)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 22 126 378 1330 977 5902 25 0 0 0 0 0 73.8 (F)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 22 126 378 1331 976 5903 24 0 0 0 0 0 73.8 (F)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 233 315 328 1900 989 4992 3 0 0 0 0 0 73.2 (F)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 231 301 335 1898 1011 4981 3 0 0 0 0 0 73.2 (F)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 0 0 0 0 552 468 493 1360 956 3019 834 808 259 11 29 29 73.8 (F)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0 0 0 0 720 331 441 3253 981 3034 0 0 0 0 0 0 72.0 (F)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 963 329 349 3764 831 2524 0 0 0 0 0 0 71.6 (F)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 966 324 352 3766 810 2542 0 0 0 0 0 0 71.6 (F)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 1102 259 327 3712 664 2696 0 0 0 0 0 0 71.6 (F)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0 0 0 0 1098 260 368 3691 745 2598 0 0 0 0 0 0 71.5 (F)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 818 303 404 2822 980 3425 8 0 0 0 2 2 72.1 (F)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 821 301 404 2825 970 3431 8 0 0 0 2 2 72.1 (F)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 990 270 353 2961 836 3344 6 0 0 0 0 0 71.9 (F)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 994 266 380 3004 830 3280 6 0 0 0 1 1 71.9 (F)

Zone < 30 (%) 30-35 (%) 35-40 (%) 40-45 (%) 45-50 (%) 50-55 (%) 55-60 (%) 60-65 (%) 65-70 (%) 70-75 (%) 75-80 (%) >= 80 (%) Mean Relative Humidity (%)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 5772 745 645 829 556 193 20 0 0 0 0 0 23.2 (%)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 4322 875 901 757 790 660 371 80 4 0 0 0 31.8 (%)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 4318 880 900 759 785 657 374 83 4 0 0 0 31.8 (%)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 4404 878 910 856 877 596 201 38 0 0 0 0 30.9 (%)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 4395 847 937 823 955 593 185 24 1 0 0 0 30.9 (%)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 4661 912 870 723 758 576 230 30 0 0 0 0 30.1 (%)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 4659 914 871 725 763 573 227 28 0 0 0 0 30.1 (%)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 4632 926 960 904 794 460 81 3 0 0 0 0 29.6 (%)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 4608 906 911 886 875 428 137 9 0 0 0 0 29.8 (%)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 5782 750 639 822 556 192 19 0 0 0 0 0 23.1 (%)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 4375 870 894 757 774 660 348 79 3 0 0 0 31.5 (%)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 4374 872 894 761 772 658 345 81 3 0 0 0 31.5 (%)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 4455 862 927 835 871 584 192 34 0 0 0 0 30.7 (%)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 4458 839 922 822 940 574 182 22 1 0 0 0 30.7 (%)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 4692 923 851 720 753 574 221 26 0 0 0 0 29.9 (%)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 4691 915 858 719 758 570 221 28 0 0 0 0 29.9 (%)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 4669 908 938 848 792 481 117 7 0 0 0 0 29.6 (%)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 4664 895 903 871 865 429 127 6 0 0 0 0 29.6 (%)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 5784 749 638 820 556 193 20 0 0 0 0 0 23.1 (%)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 4399 860 886 756 771 656 350 79 3 0 0 0 31.4 (%)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 4396 866 889 753 769 660 343 81 3 0 0 0 31.4 (%)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 4484 856 917 827 863 578 200 35 0 0 0 0 30.5 (%)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 4486 832 913 820 925 575 185 23 1 0 0 0 30.5 (%)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 4708 910 850 722 749 574 221 26 0 0 0 0 29.9 (%)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 4700 913 858 717 751 571 220 30 0 0 0 0 29.9 (%)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 4680 907 924 839 790 485 125 10 0 0 0 0 29.5 (%)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 4690 890 891 863 855 433 131 7 0 0 0 0 29.5 (%)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 5776 751 637 825 556 194 21 0 0 0 0 0 23.1 (%)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 4414 847 882 754 773 648 359 79 4 0 0 0 31.3 (%)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 4411 861 874 752 771 652 355 80 4 0 0 0 31.3 (%)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 4509 850 902 809 866 576 210 38 0 0 0 0 30.4 (%)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 4509 830 900 800 923 583 188 26 1 0 0 0 30.4 (%)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 4719 906 843 720 744 578 220 30 0 0 0 0 29.8 (%)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 4716 903 850 711 753 572 225 30 0 0 0 0 29.8 (%)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 4708 890 910 830 790 489 128 15 0 0 0 0 29.4 (%)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 4708 884 883 851 855 432 139 8 0 0 0 0 29.4 (%)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 5770 752 638 827 555 197 21 0 0 0 0 0 23.2 (%)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 4418 836 882 754 775 650 362 79 4 0 0 0 31.3 (%)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 4415 843 880 752 772 656 357 81 4 0 0 0 31.3 (%)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 4517 849 888 807 864 584 210 39 2 0 0 0 30.4 (%)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 4517 831 882 801 918 593 189 27 2 0 0 0 30.4 (%)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 4715 911 840 718 744 581 220 31 0 0 0 0 29.8 (%)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 4712 906 847 711 751 573 229 31 0 0 0 0 29.8 (%)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 4717 881 907 824 793 491 132 15 0 0 0 0 29.4 (%)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 4713 879 878 854 845 438 144 9 0 0 0 0 29.4 (%)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 5764 752 634 835 554 200 21 0 0 0 0 0 23.2 (%)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 4402 833 868 758 788 663 365 78 5 0 0 0 31.4 (%)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 4402 837 866 758 778 673 361 79 6 0 0 0 31.4 (%)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 4514 836 888 808 867 587 219 39 2 0 0 0 30.4 (%)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 4511 819 885 798 919 601 196 28 3 0 0 0 30.4 (%)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 4700 902 852 718 752 579 224 33 0 0 0 0 29.9 (%)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 4698 900 856 713 756 573 232 32 0 0 0 0 29.9 (%)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 4707 880 905 822 794 498 138 16 0 0 0 0 29.4 (%)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 4703 876 870 861 847 441 152 10 0 0 0 0 29.4 (%)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 5738 742 645 833 573 197 32 0 0 0 0 0 23.4 (%)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 4352 813 877 742 810 690 390 76 10 0 0 0 31.6 (%)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 4351 815 879 743 812 684 390 76 10 0 0 0 31.6 (%)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 4497 797 884 820 887 595 231 45 4 0 0 0 30.5 (%)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 4493 792 875 801 941 615 201 39 3 0 0 0 30.5 (%)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 4639 893 856 737 766 584 246 39 0 0 0 0 30.1 (%)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 4633 892 857 740 769 582 246 41 0 0 0 0 30.1 (%)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 4676 865 892 827 828 497 154 21 0 0 0 0 29.6 (%)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 4665 873 863 858 855 473 155 18 0 0 0 0 29.6 (%)
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 5742 736 618 833 561 223 42 5 0 0 0 0 23.5 (%)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 4197 830 915 760 746 706 453 138 15 0 0 0 32.5 (%)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 4196 831 918 769 743 699 449 140 15 0 0 0 32.5 (%)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 4270 837 931 862 862 626 305 63 4 0 0 0 31.7 (%)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 4281 821 935 819 929 650 272 48 5 0 0 0 31.7 (%)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 4516 866 906 720 741 624 315 69 3 0 0 0 30.9 (%)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 4518 870 913 737 765 599 306 51 1 0 0 0 30.8 (%)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 4482 892 917 863 889 486 205 26 0 0 0 0 30.6 (%)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 5782 750 636 821 557 193 21 0 0 0 0 0 23.1 (%)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 4406 860 883 753 768 656 351 80 3 0 0 0 31.4 (%)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 4407 866 880 750 768 656 349 80 4 0 0 0 31.4 (%)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 4496 857 909 816 865 576 203 38 0 0 0 0 30.5 (%)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 4495 838 906 806 920 584 187 23 1 0 0 0 30.5 (%)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 4717 903 848 723 743 577 220 29 0 0 0 0 29.8 (%)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 4713 905 852 715 750 572 223 30 0 0 0 0 29.8 (%)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 4694 900 919 835 786 489 125 12 0 0 0 0 29.4 (%)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 4699 889 889 852 856 435 133 7 0 0 0 0 29.4 (%)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 3723 1024 930 1750 1138 118 54 20 3 0 0 0 32.8 (%)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 5654 688 620 664 675 287 130 34 7 1 0 0 24.0 (%)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 4605 734 816 698 710 656 358 153 25 5 0 0 30.1 (%)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 4611 734 816 691 708 652 363 157 23 5 0 0 30.1 (%)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 4658 778 806 727 714 597 321 133 21 5 0 0 29.6 (%)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 4658 761 775 756 751 629 279 128 20 3 0 0 29.6 (%)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 4726 805 795 682 646 631 324 130 18 3 0 0 29.5 (%)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 4725 805 800 685 642 617 337 128 18 3 0 0 29.5 (%)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 4764 808 811 736 676 562 278 105 17 3 0 0 29.0 (%)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 4756 803 789 769 726 549 249 103 14 2 0 0 29.0 (%)

Zone Overview


Area (ft^2) Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume (ft^3) Multiplier Above Ground Gross Wall Area (ft^2) Underground Gross Wall Area (ft^2) Window Glass Area (ft^2) Lighting (W/ft^2) People (ft^2/person) Plug and Process (W/ft^2)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 21.64 0.78 1075.31 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 21.64 0.78 1075.31 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 21.64 0.78 1075.31 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 21.64 0.78 1075.31 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 21.64 0.78 1075.31 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 21.64 0.78 1075.31 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 21.64 0.78 1075.31 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 43.49 0.78 1075.31 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 21.64 0.78 1075.31 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 1.11 215.06 0.7
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 21.64 0.78 1075.31 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 102.9 0.46 645.19 0.46
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 170.61 0.46 645.19 0.46
Total 84351.17 843456.88 41495.09 0.0 11177.67 0.5 656.38 0.42
Conditioned Total 84351.17 843456.88 41495.09 0.0 11177.67 0.5 656.38 0.42
Unconditioned Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Not Part of Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Heating/Cooling Calculated Design Load Design Load With Sizing Factor Calculated Design Air Flow (ft^3/min) Design Air Flow With Sizing Factor (ft^3/min) Date/Time Of Peak Outdoor Temperature at Peak Load (F) Outdoor Humidity Ratio at Peak Load (lbWater/lbAir)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Cooling 0.37 (ton) 0.41 (ton) 214.01 235.2 7/21 20:15:00 75.33 0.01
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Heating 6.14 (kBtu/h) 7.98 (kBtu/h) 152.56 197.06 1/21 09:00:00 -28.3 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 180.1 199.17 7/21 20:15:00 75.33 0.01
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 6.25 (kBtu/h) 8.13 (kBtu/h) 158.92 205.53 1/21 09:30:00 -28.3 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 175.87 194.94 7/21 20:15:00 75.33 0.01
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 6.25 (kBtu/h) 8.13 (kBtu/h) 158.92 205.53 1/21 09:30:00 -28.3 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.52 (ton) 0.58 (ton) 303.0 332.66 7/21 09:00:00 74.71 0.01
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 9.36 (kBtu/h) 12.17 (kBtu/h) 237.31 307.24 1/21 09:30:00 -28.3 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 345.38 379.28 7/21 19:00:00 78.31 0.01
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 9.43 (kBtu/h) 12.26 (kBtu/h) 239.43 309.36 1/21 09:30:00 -28.3 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.44 (ton) 0.48 (ton) 252.15 277.57 7/21 14:00:00 87.08 0.01
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 6.25 (kBtu/h) 8.13 (kBtu/h) 158.92 205.53 1/21 09:30:00 -28.3 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.44 (ton) 0.49 (ton) 256.38 281.81 7/21 14:00:00 87.08 0.01
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 6.26 (kBtu/h) 8.14 (kBtu/h) 158.92 205.53 1/21 09:30:00 -28.3 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.65 (ton) 0.71 (ton) 375.04 413.18 7/21 13:45:00 86.79 0.01
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 9.41 (kBtu/h) 12.23 (kBtu/h) 237.31 309.36 1/21 09:30:00 -28.3 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.69 (ton) 0.76 (ton) 400.47 440.73 7/21 19:00:00 78.31 0.01
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 9.43 (kBtu/h) 12.26 (kBtu/h) 239.43 309.36 1/21 09:30:00 -28.3 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Cooling 0.37 (ton) 0.41 (ton) 214.01 237.31 7/21 20:15:00 75.33 0.01
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Heating 6.09 (kBtu/h) 7.92 (kBtu/h) 150.44 197.06 1/21 09:00:00 -28.3 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.32 (ton) 0.35 (ton) 184.34 203.41 7/21 20:15:00 75.33 0.01
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 6.38 (kBtu/h) 8.29 (kBtu/h) 161.03 209.77 1/21 09:30:00 -28.3 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 180.1 197.06 7/21 20:15:00 75.33 0.01
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 6.37 (kBtu/h) 8.28 (kBtu/h) 161.03 209.77 1/21 09:30:00 -28.3 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 307.24 336.9 7/21 09:00:00 74.71 0.01
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 9.58 (kBtu/h) 12.46 (kBtu/h) 241.55 315.71 1/21 09:30:00 -28.3 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 347.5 381.4 7/21 19:00:00 78.31 0.01
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 9.65 (kBtu/h) 12.55 (kBtu/h) 243.67 317.83 1/21 09:30:00 -28.3 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.44 (ton) 0.49 (ton) 256.38 281.81 7/21 14:00:00 87.08 0.01
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 6.38 (kBtu/h) 8.29 (kBtu/h) 161.03 209.77 1/21 09:30:00 -28.3 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 258.5 283.93 7/21 14:00:00 87.08 0.01
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 6.37 (kBtu/h) 8.29 (kBtu/h) 161.03 209.77 1/21 09:30:00 -28.3 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 364.45 400.47 7/21 13:45:00 86.79 0.01
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 9.59 (kBtu/h) 12.47 (kBtu/h) 241.55 315.71 1/21 09:30:00 -28.3 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.69 (ton) 0.76 (ton) 402.59 442.85 7/21 19:00:00 78.31 0.01
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 9.65 (kBtu/h) 12.55 (kBtu/h) 243.67 317.83 1/21 09:30:00 -28.3 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Cooling 0.37 (ton) 0.41 (ton) 214.01 237.31 7/21 20:15:00 75.33 0.01
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Heating 6.14 (kBtu/h) 7.98 (kBtu/h) 152.56 197.06 1/21 09:00:00 -28.3 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.32 (ton) 0.35 (ton) 184.34 203.41 7/21 20:15:00 75.33 0.01
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 6.5 (kBtu/h) 8.45 (kBtu/h) 165.27 214.01 1/21 09:30:00 -28.3 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 180.1 199.17 7/21 20:15:00 75.33 0.01
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 6.5 (kBtu/h) 8.44 (kBtu/h) 163.15 214.01 1/21 09:30:00 -28.3 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 307.24 339.02 7/21 09:00:00 74.71 0.01
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 9.77 (kBtu/h) 12.71 (kBtu/h) 247.91 322.07 1/21 09:30:00 -28.3 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 347.5 383.52 7/21 19:00:00 78.31 0.01
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 9.85 (kBtu/h) 12.8 (kBtu/h) 247.91 324.19 1/21 09:30:00 -28.3 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.44 (ton) 0.49 (ton) 256.38 283.93 7/21 14:00:00 87.08 0.01
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 6.5 (kBtu/h) 8.45 (kBtu/h) 165.27 214.01 1/21 09:30:00 -28.3 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 260.62 286.05 7/21 14:00:00 87.08 0.01
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 6.5 (kBtu/h) 8.44 (kBtu/h) 163.15 214.01 1/21 09:30:00 -28.3 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 364.45 400.47 7/21 13:45:00 86.79 0.01
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 9.77 (kBtu/h) 12.71 (kBtu/h) 247.91 322.07 1/21 09:30:00 -28.3 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.7 (ton) 0.77 (ton) 402.59 442.85 7/21 19:00:00 78.31 0.01
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 9.85 (kBtu/h) 12.8 (kBtu/h) 247.91 324.19 1/21 09:30:00 -28.3 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Cooling 0.37 (ton) 0.41 (ton) 214.01 237.31 7/21 20:15:00 75.33 0.01
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Heating 6.24 (kBtu/h) 8.12 (kBtu/h) 154.68 201.29 1/21 09:00:00 -28.3 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.32 (ton) 0.35 (ton) 184.34 203.41 7/21 20:00:00 75.83 0.01
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 6.69 (kBtu/h) 8.7 (kBtu/h) 169.51 220.36 1/21 09:30:00 -28.3 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 180.1 199.17 7/21 20:00:00 75.83 0.01
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 6.69 (kBtu/h) 8.7 (kBtu/h) 169.51 220.36 1/21 09:30:00 -28.3 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 307.24 336.9 7/21 09:00:00 74.71 0.01
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 10.08 (kBtu/h) 13.1 (kBtu/h) 254.27 330.55 1/21 09:30:00 -28.3 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 349.62 383.52 7/21 19:00:00 78.31 0.01
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 10.15 (kBtu/h) 13.2 (kBtu/h) 256.38 332.66 1/21 09:30:00 -28.3 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 258.5 283.93 7/21 14:00:00 87.08 0.01
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 6.69 (kBtu/h) 8.7 (kBtu/h) 169.51 220.36 1/21 09:30:00 -28.3 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 260.62 286.05 7/21 14:00:00 87.08 0.01
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 6.69 (kBtu/h) 8.7 (kBtu/h) 169.51 220.36 1/21 09:30:00 -28.3 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 364.45 402.59 7/21 13:45:00 86.79 0.01
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 10.08 (kBtu/h) 13.1 (kBtu/h) 254.27 330.55 1/21 09:30:00 -28.3 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.7 (ton) 0.77 (ton) 402.59 442.85 7/21 19:00:00 78.31 0.01
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 10.15 (kBtu/h) 13.2 (kBtu/h) 256.38 332.66 1/21 09:30:00 -28.3 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Cooling 0.37 (ton) 0.41 (ton) 214.01 237.31 7/21 20:15:00 75.33 0.01
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Heating 6.3 (kBtu/h) 8.19 (kBtu/h) 156.8 203.41 1/21 09:00:00 -28.3 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.32 (ton) 0.35 (ton) 184.34 203.41 7/21 20:00:00 75.83 0.01
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 6.79 (kBtu/h) 8.82 (kBtu/h) 171.63 222.48 1/21 09:30:00 -28.3 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 180.1 199.17 7/21 20:00:00 75.83 0.01
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 6.78 (kBtu/h) 8.82 (kBtu/h) 171.63 222.48 1/21 09:30:00 -28.3 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 307.24 336.9 7/21 09:00:00 74.71 0.01
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 10.21 (kBtu/h) 13.27 (kBtu/h) 258.5 334.78 1/21 09:30:00 -28.3 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 349.62 383.52 7/21 19:00:00 78.31 0.01
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 10.29 (kBtu/h) 13.38 (kBtu/h) 260.62 339.02 1/21 09:30:00 -28.3 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 258.5 283.93 7/21 14:00:00 87.08 0.01
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 6.79 (kBtu/h) 8.82 (kBtu/h) 171.63 222.48 1/21 09:30:00 -28.3 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 260.62 288.17 7/21 14:00:00 87.08 0.01
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 6.78 (kBtu/h) 8.82 (kBtu/h) 171.63 222.48 1/21 09:30:00 -28.3 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 366.57 402.59 7/21 13:45:00 86.79 0.01
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 10.21 (kBtu/h) 13.27 (kBtu/h) 258.5 334.78 1/21 09:30:00 -28.3 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.7 (ton) 0.77 (ton) 402.59 442.85 7/21 19:00:00 78.31 0.01
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 10.29 (kBtu/h) 13.38 (kBtu/h) 260.62 339.02 1/21 09:30:00 -28.3 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Cooling 0.37 (ton) 0.41 (ton) 216.13 237.31 7/21 20:15:00 75.33 0.01
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Heating 6.44 (kBtu/h) 8.37 (kBtu/h) 158.92 207.65 1/21 09:00:00 -28.3 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.32 (ton) 0.35 (ton) 186.46 203.41 7/21 20:00:00 75.83 0.01
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 6.94 (kBtu/h) 9.02 (kBtu/h) 175.87 228.84 1/21 09:30:00 -28.3 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 182.22 199.17 7/21 20:00:00 75.83 0.01
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 6.93 (kBtu/h) 9.01 (kBtu/h) 175.87 228.84 1/21 09:30:00 -28.3 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 305.12 336.9 7/21 09:00:00 74.71 0.01
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 10.4 (kBtu/h) 13.53 (kBtu/h) 262.74 341.14 1/21 09:30:00 -28.3 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 349.62 383.52 7/21 19:00:00 78.31 0.01
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 10.48 (kBtu/h) 13.63 (kBtu/h) 264.86 345.38 1/21 09:30:00 -28.3 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 258.5 283.93 7/21 14:00:00 87.08 0.01
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 6.94 (kBtu/h) 9.02 (kBtu/h) 175.87 228.84 1/21 09:30:00 -28.3 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 260.62 288.17 7/21 14:00:00 87.08 0.01
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 6.93 (kBtu/h) 9.01 (kBtu/h) 175.87 228.84 1/21 09:30:00 -28.3 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 366.57 402.59 7/21 13:45:00 86.79 0.01
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 10.4 (kBtu/h) 13.53 (kBtu/h) 262.74 341.14 1/21 09:30:00 -28.3 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.7 (ton) 0.77 (ton) 402.59 442.85 7/21 19:00:00 78.31 0.01
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 10.48 (kBtu/h) 13.63 (kBtu/h) 264.86 345.38 1/21 09:30:00 -28.3 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Cooling 0.38 (ton) 0.42 (ton) 220.36 243.67 7/21 20:15:00 75.33 0.01
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Heating 7.25 (kBtu/h) 9.43 (kBtu/h) 180.1 233.08 1/21 09:00:00 -28.3 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.33 (ton) 0.36 (ton) 192.82 211.89 7/21 20:00:00 75.83 0.01
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 7.61 (kBtu/h) 9.9 (kBtu/h) 192.82 250.03 1/21 09:30:00 -28.3 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.32 (ton) 0.36 (ton) 186.46 205.53 7/21 20:00:00 75.83 0.01
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 7.61 (kBtu/h) 9.89 (kBtu/h) 192.82 250.03 1/21 09:30:00 -28.3 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.52 (ton) 0.58 (ton) 303.0 332.66 7/21 09:00:00 74.71 0.01
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 11.12 (kBtu/h) 14.45 (kBtu/h) 277.57 360.21 1/21 09:00:00 -28.3 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.62 (ton) 0.68 (ton) 358.09 394.11 7/21 19:00:00 78.31 0.01
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 11.2 (kBtu/h) 14.56 (kBtu/h) 277.57 362.33 1/21 09:00:00 -28.3 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 262.74 288.17 7/21 14:00:00 87.08 0.01
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 7.61 (kBtu/h) 9.9 (kBtu/h) 192.82 250.03 1/21 09:30:00 -28.3 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.46 (ton) 0.51 (ton) 266.98 292.41 7/21 14:00:00 87.08 0.01
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 7.61 (kBtu/h) 9.89 (kBtu/h) 192.82 250.03 1/21 09:30:00 -28.3 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.64 (ton) 0.71 (ton) 370.8 408.94 7/21 13:45:00 86.79 0.01
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 11.12 (kBtu/h) 14.45 (kBtu/h) 277.57 360.21 1/21 09:00:00 -28.3 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.71 (ton) 0.78 (ton) 411.06 453.44 7/21 19:00:00 78.31 0.01
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 11.2 (kBtu/h) 14.56 (kBtu/h) 277.57 362.33 1/21 09:00:00 -28.3 0.0
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN Cooling 0.36 (ton) 0.39 (ton) 207.65 228.84 7/21 09:00:00 74.71 0.01
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN Heating 6.67 (kBtu/h) 8.67 (kBtu/h) 165.27 216.13 1/21 09:00:00 -28.3 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.31 (ton) 165.27 180.1 7/21 20:00:00 75.83 0.01
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 5.99 (kBtu/h) 7.78 (kBtu/h) 150.44 197.06 1/21 09:30:00 -28.3 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.27 (ton) 0.3 (ton) 158.92 175.87 7/21 20:00:00 75.83 0.01
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 5.99 (kBtu/h) 7.78 (kBtu/h) 150.44 197.06 1/21 09:30:00 -28.3 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.56 (ton) 0.61 (ton) 324.19 355.97 7/21 09:00:00 74.71 0.01
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 8.88 (kBtu/h) 11.54 (kBtu/h) 220.36 286.05 1/21 09:00:00 -28.3 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.59 (ton) 0.65 (ton) 343.26 377.16 7/21 19:00:00 78.31 0.01
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 8.94 (kBtu/h) 11.62 (kBtu/h) 222.48 288.17 1/21 09:00:00 -28.3 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 260.62 286.05 7/21 13:45:00 86.79 0.01
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 5.99 (kBtu/h) 7.79 (kBtu/h) 150.44 197.06 1/21 09:30:00 -28.3 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.46 (ton) 0.51 (ton) 269.1 294.52 7/21 13:45:00 86.79 0.01
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 5.93 (kBtu/h) 7.71 (kBtu/h) 150.44 194.94 1/21 09:30:00 -28.3 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.68 (ton) 0.75 (ton) 396.23 436.49 7/21 17:00:00 83.93 0.01
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 8.94 (kBtu/h) 11.62 (kBtu/h) 222.48 288.17 1/21 09:00:00 -28.3 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Cooling 0.37 (ton) 0.41 (ton) 214.01 237.31 7/21 20:15:00 75.33 0.01
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Heating 6.2 (kBtu/h) 8.06 (kBtu/h) 154.68 199.17 1/21 09:00:00 -28.3 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.32 (ton) 0.35 (ton) 184.34 203.41 7/21 20:00:00 75.83 0.01
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 6.6 (kBtu/h) 8.58 (kBtu/h) 167.39 216.13 1/21 09:30:00 -28.3 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 180.1 199.17 7/21 20:15:00 75.33 0.01
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 6.6 (kBtu/h) 8.58 (kBtu/h) 167.39 216.13 1/21 09:30:00 -28.3 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 307.24 336.9 7/21 09:00:00 74.71 0.01
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 9.94 (kBtu/h) 12.92 (kBtu/h) 252.15 326.31 1/21 09:30:00 -28.3 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.6 (ton) 0.66 (ton) 347.5 383.52 7/21 19:00:00 78.31 0.01
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 10.01 (kBtu/h) 13.01 (kBtu/h) 252.15 328.43 1/21 09:30:00 -28.3 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 258.5 283.93 7/21 14:00:00 87.08 0.01
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 6.6 (kBtu/h) 8.58 (kBtu/h) 167.39 216.13 1/21 09:30:00 -28.3 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 260.62 286.05 7/21 14:00:00 87.08 0.01
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 6.6 (kBtu/h) 8.58 (kBtu/h) 167.39 216.13 1/21 09:30:00 -28.3 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 364.45 400.47 7/21 13:45:00 86.79 0.01
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 9.94 (kBtu/h) 12.92 (kBtu/h) 252.15 326.31 1/21 09:30:00 -28.3 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.7 (ton) 0.77 (ton) 402.59 442.85 7/21 19:00:00 78.31 0.01
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 10.01 (kBtu/h) 13.01 (kBtu/h) 252.15 328.43 1/21 09:30:00 -28.3 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Cooling 0.92 (ton) 1.01 (ton) 529.72 582.69 7/21 13:30:00 86.52 0.01
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Heating 9.57 (kBtu/h) 12.44 (kBtu/h) 237.31 309.36 1/21 08:00:00 -28.3 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Cooling 0.49 (ton) 0.54 (ton) 283.93 311.48 7/21 15:45:00 86.07 0.01
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Heating 13.11 (kBtu/h) 17.04 (kBtu/h) 326.31 423.78 1/21 09:00:00 -28.3 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.39 (ton) 0.43 (ton) 226.72 250.03 7/21 14:45:00 87.08 0.01
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 12.63 (kBtu/h) 16.42 (kBtu/h) 313.59 408.94 1/21 09:00:00 -28.3 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.39 (ton) 0.43 (ton) 226.72 250.03 7/21 14:30:00 87.08 0.01
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 12.63 (kBtu/h) 16.42 (kBtu/h) 313.59 408.94 1/21 09:00:00 -28.3 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.72 (ton) 0.79 (ton) 417.42 459.8 7/21 09:15:00 75.67 0.01
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 15.94 (kBtu/h) 20.73 (kBtu/h) 396.23 517.01 1/21 09:00:00 -28.3 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.81 (ton) 0.89 (ton) 468.27 514.89 7/21 17:00:00 83.93 0.01
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 16.02 (kBtu/h) 20.82 (kBtu/h) 398.35 519.13 1/21 09:00:00 -28.3 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.71 (ton) 0.78 (ton) 411.06 451.32 7/21 13:45:00 86.79 0.01
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 12.63 (kBtu/h) 16.42 (kBtu/h) 313.59 408.94 1/21 09:00:00 -28.3 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.71 (ton) 0.78 (ton) 413.18 453.44 7/21 13:45:00 86.79 0.01
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 12.63 (kBtu/h) 16.42 (kBtu/h) 313.59 408.94 1/21 09:00:00 -28.3 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.86 (ton) 0.95 (ton) 497.94 546.67 7/21 13:30:00 86.52 0.01
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 15.94 (kBtu/h) 20.73 (kBtu/h) 396.23 517.01 1/21 09:00:00 -28.3 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.91 (ton) 1.0 (ton) 527.6 580.57 7/21 16:15:00 85.28 0.01
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 16.02 (kBtu/h) 20.82 (kBtu/h) 398.35 519.13 1/21 09:00:00 -28.3 0.0

Zone Equipment Detail


Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Air Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:DX:SingleSpeed Autosized Btu/h Rated COP 3.43 COP
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 68.0 to 68.0 F
(demand)
Thermal Zones Total Floor Area 83,401 ft^2 89
Thermal Zones thermostat ranges for cooling 75.2 to 75.2 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:Uncontrolled 89
(controls)
HVAC Operation Schedule Make-up air unit Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting DifferentialEnthalpy Choice
Demand Controlled Ventilation Status false Bool

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:Water Autosized gal/min Plant Loop Chilled Water Loop
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:VariableVolume Autosized cfm Pressure Rise 5.85 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 55.4 to 55.4 F
(demand)
Thermal Zones Total Floor Area 950 ft^2 1
Thermal Zones thermostat ranges for cooling 75.2 to 95.0 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:VAV:Reheat 1
(controls)
HVAC Operation Schedule VAV with Reheat Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting NoEconomizer Choice
Demand Controlled Ventilation Status false Bool

Plant Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:Chiller:Electric:EIR 16,148.75 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
OS:SetpointManager:Scheduled Control Variable - Temperature 44.6 to 44.6 F
OS:Chiller:Electric:EIR 0.00 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
(demand)
OS:Coil:Cooling:Water Air Loop VAV with Reheat
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 44.60 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:CoolingTower:SingleSpeed - Air Autosized gal/min
OS:CoolingTower:SingleSpeed (cont) - Water Autosized cfm Fan Power at Design Air Flow Rate 183,824.59 W
OS:SetpointManager:Scheduled Control Variable - Temperature 84.2 to 84.2 F
(demand)
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 84.20 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:WaterHeater:Mixed 600 gal Heater Thermal Efficiency 1.00 fraction
OS:SetpointManager:Scheduled Control Variable - Temperature 140.0 to 140.0 F
(demand)
OS:WaterUse:Connections Water Use Connections 1
OS:WaterUse:Connections Water Use Connections 2
OS:WaterUse:Connections Water Use Connections 3
OS:WaterUse:Connections Water Use Connections 4
OS:WaterUse:Connections Water Use Connections 5
OS:WaterUse:Connections Water Use Connections 6
OS:WaterUse:Connections Water Use Connections 7
OS:WaterUse:Connections Water Use Connections 8
OS:WaterUse:Connections Water Use Connections 9
OS:WaterUse:Connections Water Use Connections 10
OS:WaterUse:Connections Water Use Connections 11
OS:WaterUse:Connections Water Use Connections 12
OS:WaterUse:Connections Water Use Connections 13
OS:WaterUse:Connections Water Use Connections 14
OS:WaterUse:Connections Water Use Connections 15
OS:WaterUse:Connections Water Use Connections 16
OS:WaterUse:Connections Water Use Connections 17
OS:WaterUse:Connections Water Use Connections 18
OS:WaterUse:Connections Water Use Connections 19
OS:WaterUse:Connections Water Use Connections 20
OS:WaterUse:Connections Water Use Connections 21
OS:WaterUse:Connections Water Use Connections 22
OS:WaterUse:Connections Water Use Connections 23
OS:WaterUse:Connections Water Use Connections 24
OS:WaterUse:Connections Water Use Connections 25
OS:WaterUse:Connections Water Use Connections 26
OS:WaterUse:Connections Water Use Connections 27
OS:WaterUse:Connections Water Use Connections 28
OS:WaterUse:Connections Water Use Connections 29
OS:WaterUse:Connections Water Use Connections 30
OS:WaterUse:Connections Water Use Connections 31
OS:WaterUse:Connections Water Use Connections 32
OS:WaterUse:Connections Water Use Connections 33
OS:WaterUse:Connections Water Use Connections 34
OS:WaterUse:Connections Water Use Connections 35
OS:WaterUse:Connections Water Use Connections 36
OS:WaterUse:Connections Water Use Connections 37
OS:WaterUse:Connections Water Use Connections 38
OS:WaterUse:Connections Water Use Connections 39
OS:WaterUse:Connections Water Use Connections 40
OS:WaterUse:Connections Water Use Connections 41
OS:WaterUse:Connections Water Use Connections 42
OS:WaterUse:Connections Water Use Connections 43
OS:WaterUse:Connections Water Use Connections 44
OS:WaterUse:Connections Water Use Connections 45
OS:WaterUse:Connections Water Use Connections 46
OS:WaterUse:Connections Water Use Connections 47
OS:WaterUse:Connections Water Use Connections 48
OS:WaterUse:Connections Water Use Connections 49
OS:WaterUse:Connections Water Use Connections 50
OS:WaterUse:Connections Water Use Connections 51
OS:WaterUse:Connections Water Use Connections 52
OS:WaterUse:Connections Water Use Connections 53
OS:WaterUse:Connections Water Use Connections 54
OS:WaterUse:Connections Water Use Connections 55
OS:WaterUse:Connections Water Use Connections 56
OS:WaterUse:Connections Water Use Connections 57
OS:WaterUse:Connections Water Use Connections 58
OS:WaterUse:Connections Water Use Connections 59
OS:WaterUse:Connections Water Use Connections 60
OS:WaterUse:Connections Water Use Connections 61
OS:WaterUse:Connections Water Use Connections 62
OS:WaterUse:Connections Water Use Connections 63
OS:WaterUse:Connections Water Use Connections 64
OS:WaterUse:Connections Water Use Connections 65
OS:WaterUse:Connections Water Use Connections 66
OS:WaterUse:Connections Water Use Connections 67
OS:WaterUse:Connections Water Use Connections 68
OS:WaterUse:Connections Water Use Connections 69
OS:WaterUse:Connections Water Use Connections 70
OS:WaterUse:Connections Water Use Connections 71
OS:WaterUse:Connections Water Use Connections 72
OS:WaterUse:Connections Water Use Connections 73
OS:WaterUse:Connections Water Use Connections 74
OS:WaterUse:Connections Water Use Connections 75
OS:WaterUse:Connections Water Use Connections 76
OS:WaterUse:Connections Water Use Connections 77
OS:WaterUse:Connections Water Use Connections 78
OS:WaterUse:Connections Water Use Connections 79
OS:WaterUse:Connections Water Use Connections 80
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 50.0 to 140.0 F
Design Loop Exit Temperature 140.00 F
Loop Design Temperature Difference 9.00 R

Outdoor Air


Average Number of Occupants Nominal Number of Occupants Zone Volume (ft^3) Avg. Mechanical Ventilation (ach) Min. Mechanical Ventilation (ach) Avg. Infiltration (ach) Min. Infiltration (ach) Avg. Simple Ventilation (ach) Min. Simple Ventilation (ach)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.421 0.353 0.015 0.0 0.0 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.462 0.397 0.045 0.0 0.0 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.462 0.397 0.045 0.0 0.0 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.465 0.397 0.075 0.0 0.0 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.459 0.397 0.075 0.0 0.0 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.494 0.399 0.045 0.0 0.0 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.494 0.399 0.045 0.0 0.0 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.492 0.397 0.075 0.0 0.0 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.48 0.397 0.075 0.0 0.0 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.423 0.353 0.018 0.0 0.0 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.463 0.397 0.053 0.0 0.0 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.464 0.397 0.053 0.0 0.0 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.466 0.396 0.088 0.0 0.0 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.46 0.397 0.088 0.0 0.0 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.495 0.399 0.053 0.0 0.0 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.495 0.399 0.053 0.0 0.0 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.489 0.397 0.089 0.0 0.0 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.481 0.397 0.089 0.0 0.0 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.423 0.352 0.02 0.0 0.0 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.463 0.397 0.06 0.0 0.0 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.463 0.397 0.06 0.0 0.0 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.465 0.396 0.099 0.0 0.0 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.459 0.396 0.099 0.0 0.0 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.495 0.399 0.06 0.0 0.0 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.494 0.399 0.06 0.0 0.0 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.487 0.397 0.099 0.0 0.0 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.48 0.397 0.099 0.0 0.0 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.422 0.352 0.023 0.0 0.0 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.46 0.397 0.069 0.0 0.0 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.461 0.397 0.069 0.0 0.0 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.465 0.396 0.115 0.0 0.0 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.396 0.115 0.0 0.0 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.493 0.399 0.069 0.0 0.0 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.492 0.399 0.069 0.0 0.0 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.485 0.397 0.115 0.0 0.0 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.479 0.397 0.115 0.0 0.0 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.421 0.352 0.024 0.0 0.0 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.459 0.397 0.073 0.0 0.0 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.459 0.397 0.073 0.0 0.0 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.464 0.396 0.121 0.0 0.0 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.396 0.121 0.0 0.0 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.491 0.398 0.073 0.0 0.0 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.491 0.398 0.073 0.0 0.0 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.484 0.397 0.121 0.0 0.0 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.478 0.397 0.121 0.0 0.0 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.419 0.352 0.025 0.0 0.0 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.397 0.077 0.0 0.0 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.457 0.397 0.077 0.0 0.0 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.462 0.396 0.127 0.0 0.0 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.396 0.127 0.0 0.0 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.489 0.398 0.077 0.0 0.0 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.488 0.398 0.077 0.0 0.0 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.482 0.397 0.127 0.0 0.0 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.476 0.397 0.127 0.0 0.0 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.413 0.352 0.026 0.0 0.0 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.451 0.397 0.08 0.0 0.0 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.451 0.397 0.08 0.0 0.0 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.396 0.132 0.0 0.0 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.454 0.396 0.132 0.0 0.0 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.482 0.398 0.08 0.0 0.0 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.481 0.398 0.08 0.0 0.0 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.478 0.397 0.133 0.0 0.0 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.472 0.397 0.133 0.0 0.0 0.0
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.417 0.352 0.01 0.0 0.0 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.453 0.397 0.031 0.0 0.0 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.453 0.397 0.031 0.0 0.0 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.455 0.396 0.052 0.0 0.0 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.452 0.396 0.052 0.0 0.0 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.482 0.399 0.031 0.0 0.0 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.484 0.399 0.031 0.0 0.0 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.475 0.397 0.052 0.0 0.0 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.423 0.352 0.021 0.0 0.0 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.462 0.397 0.065 0.0 0.0 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.462 0.397 0.065 0.0 0.0 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.465 0.396 0.107 0.0 0.0 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.459 0.396 0.107 0.0 0.0 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.494 0.399 0.065 0.0 0.0 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.493 0.399 0.065 0.0 0.0 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.486 0.397 0.108 0.0 0.0 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.48 0.397 0.108 0.0 0.0 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2.37 4.42 9498 0.358 0.0 0.055 0.0 0.0 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.392 0.35 0.234 0.0 0.0 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.436 0.396 0.29 0.0 0.0 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.436 0.396 0.29 0.0 0.0 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.445 0.396 0.344 0.0 0.0 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.446 0.396 0.344 0.0 0.0 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.457 0.396 0.29 0.0 0.0 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.457 0.396 0.29 0.0 0.0 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.461 0.396 0.345 0.0 0.0 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.46 0.396 0.345 0.0 0.0 0.0

Cash Flow

No Data to Show for Cash Flow

Site and Source Summary


Total Energy (kBtu) Energy Per Total Building Area (kBtu/ft^2) Energy Per Conditioned Building Area (kBtu/ft^2)
Total Site Energy 4017000.8 47.6 47.6
Net Site Energy 4017000.8 47.6 47.6
Total Source Energy 12721847.6 150.8 150.8
Net Source Energy 12721847.6 150.8 150.8

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613

Schedule Overview


Schedule Type Limits Rules Use Count
Air Velocity Schedule Velocity 0 3
Always On Dimensionless 0 90
CHW Temp Temperature 3 1
Clothing Schedule ClothingInsulation 1 3
CW Temp Temperature 3 1
Make-up air unit Occ Sch Dimensionless 7 2
Makeup-Air Unit Supply Air Temp Temperature 0 1
NECB-A-Electric-Equipment Dimensionless 3 1
NECB-A-Lighting Dimensionless 3 1
NECB-A-Occupancy Dimensionless 3 1
NECB-A-Service Water Heating Dimensionless 3 1
NECB-A-Thermostat Setpoint-Cooling Temperature 3 3
NECB-A-Thermostat Setpoint-Heating Temperature 3 3
NECB-Activity ActivityLevel 0 90
NECB-G-Electric-Equipment Dimensionless 3 89
NECB-G-Lighting Dimensionless 3 89
NECB-G-Occupancy Dimensionless 3 89
NECB-G-Service Water Heating Dimensionless 3 79
NECB-G-Thermostat Setpoint-Cooling Temperature 3 180
NECB-G-Thermostat Setpoint-Heating Temperature 3 180
ON_OFF_ALWAYS_OFF Availability 3 89
Schedule Ruleset 10 0 1
Schedule Ruleset 100 0 1
Schedule Ruleset 101 0 1
Schedule Ruleset 102 0 1
Schedule Ruleset 103 0 1
Schedule Ruleset 104 0 1
Schedule Ruleset 105 0 1
Schedule Ruleset 106 0 1
Schedule Ruleset 107 0 1
Schedule Ruleset 108 0 1
Schedule Ruleset 109 0 1
Schedule Ruleset 11 0 1
Schedule Ruleset 110 0 1
Schedule Ruleset 111 0 1
Schedule Ruleset 112 0 1
Schedule Ruleset 113 0 1
Schedule Ruleset 114 0 1
Schedule Ruleset 115 0 1
Schedule Ruleset 116 0 1
Schedule Ruleset 117 0 1
Schedule Ruleset 118 0 1
Schedule Ruleset 119 0 1
Schedule Ruleset 12 0 1
Schedule Ruleset 120 0 1
Schedule Ruleset 121 0 1
Schedule Ruleset 122 0 1
Schedule Ruleset 123 0 1
Schedule Ruleset 124 0 1
Schedule Ruleset 125 0 1
Schedule Ruleset 126 0 1
Schedule Ruleset 127 0 1
Schedule Ruleset 128 0 1
Schedule Ruleset 129 0 1
Schedule Ruleset 13 0 1
Schedule Ruleset 130 0 1
Schedule Ruleset 131 0 1
Schedule Ruleset 132 0 1
Schedule Ruleset 133 0 1
Schedule Ruleset 134 0 1
Schedule Ruleset 135 0 1
Schedule Ruleset 136 0 1
Schedule Ruleset 137 0 1
Schedule Ruleset 138 0 1
Schedule Ruleset 139 0 1
Schedule Ruleset 14 0 1
Schedule Ruleset 140 0 1
Schedule Ruleset 141 0 1
Schedule Ruleset 142 0 1
Schedule Ruleset 143 0 1
Schedule Ruleset 144 0 1
Schedule Ruleset 145 0 1
Schedule Ruleset 146 0 1
Schedule Ruleset 147 0 1
Schedule Ruleset 148 0 1
Schedule Ruleset 149 0 1
Schedule Ruleset 15 0 1
Schedule Ruleset 150 0 1
Schedule Ruleset 151 0 1
Schedule Ruleset 152 0 1
Schedule Ruleset 153 0 1
Schedule Ruleset 154 0 1
Schedule Ruleset 155 0 1
Schedule Ruleset 156 0 1
Schedule Ruleset 157 0 1
Schedule Ruleset 158 0 1
Schedule Ruleset 159 0 1
Schedule Ruleset 16 0 1
Schedule Ruleset 160 0 1
Schedule Ruleset 161 0 1
Schedule Ruleset 162 0 1
Schedule Ruleset 163 0 1
Schedule Ruleset 164 0 1
Schedule Ruleset 165 0 1
Schedule Ruleset 166 0 1
Schedule Ruleset 167 0 1
Schedule Ruleset 168 0 1
Schedule Ruleset 169 0 1
Schedule Ruleset 17 0 1
Schedule Ruleset 170 0 1
Schedule Ruleset 171 0 1
Schedule Ruleset 172 0 1
Schedule Ruleset 173 0 1
Schedule Ruleset 174 0 1
Schedule Ruleset 175 0 1
Schedule Ruleset 176 0 1
Schedule Ruleset 177 0 1
Schedule Ruleset 178 0 1
Schedule Ruleset 179 0 1
Schedule Ruleset 18 0 1
Schedule Ruleset 180 0 1
Schedule Ruleset 181 0 1
Schedule Ruleset 182 0 1
Schedule Ruleset 183 0 1
Schedule Ruleset 184 0 1
Schedule Ruleset 185 0 1
Schedule Ruleset 186 0 1
Schedule Ruleset 187 0 1
Schedule Ruleset 188 0 1
Schedule Ruleset 189 0 1
Schedule Ruleset 19 0 1
Schedule Ruleset 190 0 1
Schedule Ruleset 191 0 1
Schedule Ruleset 192 0 1
Schedule Ruleset 193 0 1
Schedule Ruleset 194 0 1
Schedule Ruleset 195 0 1
Schedule Ruleset 196 0 1
Schedule Ruleset 197 0 1
Schedule Ruleset 198 0 1
Schedule Ruleset 199 0 1
Schedule Ruleset 20 0 1
Schedule Ruleset 200 0 1
Schedule Ruleset 201 0 1
Schedule Ruleset 202 0 1
Schedule Ruleset 203 0 1
Schedule Ruleset 204 0 1
Schedule Ruleset 205 0 1
Schedule Ruleset 206 0 1
Schedule Ruleset 207 0 1
Schedule Ruleset 208 0 1
Schedule Ruleset 209 0 1
Schedule Ruleset 21 0 1
Schedule Ruleset 210 0 1
Schedule Ruleset 211 0 1
Schedule Ruleset 212 0 1
Schedule Ruleset 213 0 1
Schedule Ruleset 214 0 1
Schedule Ruleset 215 0 1
Schedule Ruleset 216 0 1
Schedule Ruleset 217 0 1
Schedule Ruleset 218 0 1
Schedule Ruleset 219 0 1
Schedule Ruleset 22 0 1
Schedule Ruleset 220 0 1
Schedule Ruleset 221 0 1
Schedule Ruleset 222 0 1
Schedule Ruleset 223 0 1
Schedule Ruleset 224 0 1
Schedule Ruleset 225 0 1
Schedule Ruleset 226 0 1
Schedule Ruleset 227 0 1
Schedule Ruleset 228 0 1
Schedule Ruleset 229 0 1
Schedule Ruleset 23 0 1
Schedule Ruleset 230 0 1
Schedule Ruleset 231 0 1
Schedule Ruleset 232 0 1
Schedule Ruleset 233 0 1
Schedule Ruleset 234 0 1
Schedule Ruleset 235 0 1
Schedule Ruleset 236 0 1
Schedule Ruleset 237 0 1
Schedule Ruleset 238 0 1
Schedule Ruleset 239 0 1
Schedule Ruleset 24 0 1
Schedule Ruleset 240 0 1
Schedule Ruleset 241 0 1
Schedule Ruleset 242 0 1
Schedule Ruleset 25 0 1
Schedule Ruleset 26 0 1
Schedule Ruleset 27 0 1
Schedule Ruleset 28 0 1
Schedule Ruleset 29 0 1
Schedule Ruleset 3 0 1
Schedule Ruleset 30 0 1
Schedule Ruleset 31 0 1
Schedule Ruleset 32 0 1
Schedule Ruleset 33 0 1
Schedule Ruleset 34 0 1
Schedule Ruleset 35 0 1
Schedule Ruleset 36 0 1
Schedule Ruleset 37 0 1
Schedule Ruleset 38 0 1
Schedule Ruleset 39 0 1
Schedule Ruleset 4 0 1
Schedule Ruleset 40 0 1
Schedule Ruleset 41 0 1
Schedule Ruleset 42 0 1
Schedule Ruleset 43 0 1
Schedule Ruleset 44 0 1
Schedule Ruleset 45 0 1
Schedule Ruleset 46 0 1
Schedule Ruleset 47 0 1
Schedule Ruleset 48 0 1
Schedule Ruleset 49 0 1
Schedule Ruleset 5 0 1
Schedule Ruleset 50 0 1
Schedule Ruleset 51 0 1
Schedule Ruleset 52 0 1
Schedule Ruleset 53 0 1
Schedule Ruleset 54 0 1
Schedule Ruleset 55 0 1
Schedule Ruleset 56 0 1
Schedule Ruleset 57 0 1
Schedule Ruleset 58 0 1
Schedule Ruleset 59 0 1
Schedule Ruleset 6 0 1
Schedule Ruleset 60 0 1
Schedule Ruleset 61 0 1
Schedule Ruleset 62 0 1
Schedule Ruleset 63 0 1
Schedule Ruleset 64 0 1
Schedule Ruleset 65 0 1
Schedule Ruleset 66 0 1
Schedule Ruleset 67 0 1
Schedule Ruleset 68 0 1
Schedule Ruleset 69 0 1
Schedule Ruleset 7 0 1
Schedule Ruleset 70 0 1
Schedule Ruleset 71 0 1
Schedule Ruleset 72 0 1
Schedule Ruleset 73 0 1
Schedule Ruleset 74 0 1
Schedule Ruleset 75 0 1
Schedule Ruleset 76 0 1
Schedule Ruleset 77 0 1
Schedule Ruleset 78 0 1
Schedule Ruleset 79 0 1
Schedule Ruleset 8 0 1
Schedule Ruleset 80 0 1
Schedule Ruleset 81 0 1
Schedule Ruleset 82 0 1
Schedule Ruleset 83 0 1
Schedule Ruleset 84 0 1
Schedule Ruleset 85 0 1
Schedule Ruleset 86 0 1
Schedule Ruleset 87 0 1
Schedule Ruleset 88 0 1
Schedule Ruleset 89 0 1
Schedule Ruleset 9 0 1
Schedule Ruleset 90 0 1
Schedule Ruleset 91 0 1
Schedule Ruleset 92 0 1
Schedule Ruleset 93 0 1
Schedule Ruleset 94 0 1
Schedule Ruleset 95 0 1
Schedule Ruleset 96 0 1
Schedule Ruleset 97 0 1
Schedule Ruleset 98 0 1
Schedule Ruleset 99 0 1
Service Water Loop Temp - 140F Temperature 0 2
Supply Air Temp Temperature 0 1
VAV with Reheat Occ Sch Dimensionless 7 2
Water Heater Ambient Temp Schedule - 70F Temperature 0 1
Work Efficiency Schedule Dimensionless 0 3